Product Features:

  • Rated output: 360W
  • 6 speaker line outputs
  • 8 control inputs & 8 control outputs for general purpose
  • Connection to system management amplifier via VM Link
  • 6 control inputs for emergency purpose, & 3 control outputs for status information
  • System management amplifier can be expanded by connecting up to 9 extension amplifiers

Specifications:

VM-3360E

VM-3240E

Power source

230 V AC
50/60 Hz (24 V DC)
230 V AC
50/60 Hz (24 V DC)

Rated output

Total: 6 zones @ 360 W
Total: 6 zones @ 240 W

Frequency response

50 Hz – 20 kHz (at 1/3 rated output)
50 Hz – 20 kHz (at 1/3 rated output)

Distortion

< 0.7 %
< 0.7 %

Power consumption

380 W (according to EN 60065)
850 W – w/ rated output signal
260 W (according to EN 60065)
600 W – w/ rated output signal

S/N ratio

85 dB (or more)
85 dB (or more)

Inputs

External amplifier Input: 100 V Line;
  • Removable terminal block (14 pins)

Local input -50 dBV (Mic) / -10 dBV (Line), 600 Ω / electronically balanced;

  • Removable terminal block (14 x 2 pins)
External amplifier Input: 100 V Line;
  • Removable terminal block (14 pins)
Local input -50 dBV (Mic) / -10 dBV (Line), 600 Ω / electronically balanced;;
  • Removable terminal block (14 x 2 pins)

Outputs

Speaker output 1 – 6: Total within rated output;
  • Removable terminal block (14 pins)
Direct output from internal or external amplifier;
  • Removable terminal block (16 pins)
Speaker output 1 – 6: Total within rated output;
  • Removable terminal block (14 pins)
Direct output from internal or external amplifier;
  • Removable terminal block (16 pins)

Control input

Input 1 – 8: No-Voltage make contact input
Open voltage: 24 V DC
Short-circuit current: under 2 mA;
  • Removable terminal block (14 pins)
Input 1 – 8: No-Voltage make contact input
Open voltage: 24 V DC
Short-circuit current: under 2 mA;
  • Removable terminal block (14 pins)

Control output

Output 1 – 8: Isolated open collector output
Withstand voltage: 30 V DC
Operating current: under 10 mA;
  • Removable terminal block (14 pins)
Output 1 – 8: Isolated open collector output
Withstand voltage: 30 V DC
Operating current: under 10 mA;
  • Removable terminal block (14 pins)

Indicator

Power; 5-segment bargraph level meter, selected zone, emergency zone active, communication fault, CPU fault
Power; 5-segment bargraph level meter, selected zone, emergency zone active, communication fault, CPU fault

Operating humidity

5 to 95% RH (No Condensation)
5 to 95% RH (No Condensation)

Operating

temperature

-5°C to +45°C
-5°C to +45°C

Finish

Aluminium, steel plate, hairline, surface-treated, paint, black
Aluminium, steel plate, hairline, surface-treated, paint, black

Dimensions

482 x 132.6 x 407 mm (W x H x D)
482 x 132.6 x 407 mm (W x H x D)

Weight

19 kg
16.5 kg

Accessory

(included)

  • Plastic foot, x4
  • Link cable: 3m, x2
  • AC power cord: 2m
  • Plastic foot mounting screw, x4
  • Removable terminal plug (14 pins), x3
  • Removable terminal plug (16 pins), x1
  • Plastic foot, x4
  • Link cable: 3m, x2
  • AC power cord: 2m
  • Plastic foot mounting screw, x4
  • Removable terminal plug (14 pins), x3
  • Removable terminal plug (16 pins), x1

Data Sheets

Brochure
Data Sheet

Additional information